2 Anni
PPF20A0400
Prodotto nuovo
Overview
The FSP Clippers RT Series is a high-quality online double conversion UPS designed for both rack and tower configurations. It offers high efficiency, which helps lower the total cost of ownership for customers. The internal hot-swappable battery enhances system reliability and minimizes mean time to repair (MTTR). Additionally, the UPS features a parallel function that allows for future equipment expansion. Its specialized firmware is adaptable for various applications, including laser printers and ultrasound devices, and it supports extended backup times with battery monitoring capabilities.
Features
Model | Clippers RT 1K | Clippers RT 2K | Clippers RT 3K |
Capacity | 1000 VA / 1000W | 2000 VA / 2000W | 3000 VA / 3000W |
Input Voltage Range | 160-300 VAC ±5% | ||
Input Frequency | 40Hz ~ 70Hz | ||
Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) | ||
Output Voltage | ± 1% (Batt. Mode) | ||
Output Frequency Range | 46 Hz ~ 54 Hz or 56Hz ~ 64 Hz (Synchronized Range) 50 Hz or 60 Hz ±0.1 Hz (Batt. Mode) |
||
Current Crest Ratio | 3:1 | ||
Harmonic Distortion | ≤ 2 % THD (Linear Load) ≤ 4 % THD (Non-linear Load) |
||
Output Transfer Time (Typical) | Zero (AC to DC) 4ms (Inverter to Bypass) |
||
Output Waveform (Batt. Mode) | Pure Sinewave | ||
Battery Type & Number | 12V / 9Ah x 2 | 12V / 9Ah x 4 | 12V / 9Ah x 6 |
EMC/ Safety | EMC EN62040-2 C2 for CE models | ||
Typical Recharge Time (up to 90% capacity) | 3 hours | ||
Indicators / AC Mode | Yes | ||
Indicators / Battery Mode | Yes | ||
Indicators / Battery level | Yes | ||
Indicators / Load level | Yes | ||
Indicators / Bypass mode | Yes | ||
Indicators / Fault | Yes | ||
Alarm / Battery Mode | Sounding every 4 seconds | ||
Alarm / Low Battery | Sounding every second (Batt. Mode) | ||
Alarm / Overload | Sounding twice per second | ||
Alarm / Fault | Continuously sounding | ||
Physical Dimension (mm) | 438 x 88 x 410 | 438 x 88 x 510 | 438 x 88 x 630 |
Physical Net Weight (kg) Standard Model |
11.6 | 19.5 | 27.5 |
Backup Time | Full load up to 33 minutes (with 2 external battery pack) | ||
Operating Environment / Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | ||
Operating Environment / Noise Level | 50dB @ 1 Meter | ||
Management / Optional USB / RS-232 Port | Supports Windows® 98/XP/2000/Vista/7/8/10, Windows® Server 2000/2003/2008/2012/2016, Linux, and MAC | ||
Optional SNMP | Power management from SNMP manager and web browser |